Safety Notice - This is a gas-fired product, and only professionals who are qualified to work on live gas and 120v electrical equipment should do so. If you are in need of a qualified professional in your area, please use this contractor search page.
As with all combustion equipment, there are certain maintenance points that should be checked at least once per year:
1. The exhaust venting and vent termination should be checked to ensure that there are no blockages, damage, or flue gas leaks.
2. The exhaust connector should be in place, slope upwards away from the furnace, and be free of holes, damage, or corrosion.
3. The interior of the furnace should be inspected for loose or damaged wiring.
4. The heat exchangers and fan blower should be inspected for corrosion, deterioration, or debris.
5. The return air ducting should be physically sound, fully sealed to the furnace cabinet, and terminates outside the space that contains the furnace.
6. The physical support of the furnace must be sound, with no sagging, cracks, or gaps around the base so as to provide a seal between the support and the base of the furnace.
7. There must be no obvious signs of deterioration or damage to the furnace.
8. The pilot and burner flames must be in good condition and adjusted properly.
9. The condensate drain and trap should be free of leaks or cracks.
10. Drain the trap, clean it, and fill with fresh water.
11. The flame sensor should be carefully cleaned and tested.
12. Installer-supplied air filters should be cleaned, or replaced.
For further details and specific instructions for the details listed above, please download the Installation, Operation, and Maintenance Manual. (PDF 4.2 MB)