Air to Air Heat Pump Systems Troubleshooting
IDS/IDP Screenings are available for Error Codes.
IDS/IDP Screenings
2 IDS / IDP - ATL Error Code
2 IDS / IDP - ATL Error Code
2.1.1 ISM Notes
General Reason |
CC-HTPAA |
Specific Reason |
CC-ATL |
2.1.2 Error Code Information
Error Code | ATL |
---|---|
Error Code Meaning |
Ambient Temperature Limited. Cooling (T4>=125 F or T4<15 F) Heating (T4>=86 F or T4<-4 F) |
Possible Causes |
|
Tools Needed
Refrigerant gauges, Digital multimeter. If no tools, no tier 2 transfer. Details of how to restart the unit can be found in the manual found here.
If you need to reference the wiring diagram for the unit, please click here.
If the callers needs a copy of the manual, email them the link below and advise them to select the manual for their specific model.
3.1.3 Enhanced Screening Questions (What to do?)
IDS / IDP - C3/C4 Error Code
3 IDS / IDP - ATL Error Code
3.1.1 ISM Notes
General Reason |
CC-HTPAA |
Specific Reason |
CC-C3/C4 |
3.1.2 Error Code Information
Error Code | C3 |
---|---|
Error Code Meaning | The condenser coil sensor is seated fault in cooling (T3). (PI control running) and (T3<T4-3 F for 10 minutes) |
Possible Causes |
|
Tools Needed
Refrigerant gauges, Digital multimeter. If no tools, no tier 2 transfer. Details of how to restart the unit can be found in the manual found here.
If you need to reference the wiring diagram for the unit, please click here.
If the callers needs a copy of the manual, email them the link below and advise them to select the manual for their specific model.
3.1.3 Enhanced Screening Questions (What to do?)
Step 1. Check location of T3 sensor.
- Sensor should be located on the outdoor coil, below and to the left of the control board on a "U" bend. If it is not there, have the caller locate the sensor connection on the board and follow the wires to the sensor so they can relocate it.
- If the sensor is in the right place, go to step 2.
Step 2. Check the T4, T3 and/or T3L temperature sensor.
- Measure sensor resistance T3, T3L, T4, T5 and TF (T3L only for IDP and 15, 20 SEER IDS models).
- 18 SEER will only have T3 sensor.
- 15, 20 SEER and IDP Packaged units will have T3 and T3L, so test both.
T3/T4/T3L sensors are 10k sensors. Example: 77 degrees sensor should read 10,000 OHMS Use the chart below to compare the ohm reading with the temperature reading.
- Make note of the resistance and temperature readings in ISM.
- If the sensor ohm reading doesn't match the temperature reading, replace the sensor.
Step 3. If everything tests OK, transfer the caller to tier 2.